HD active cold door

A cabinet equipped with a hydro-cooled door to house up to 45 kW of equipment without heating the air leaving the cabinet, and without disturbing server ventilation.
Heated air leaving the servers is cooled by a chilled-water exchanger housed in the rear door. Fans compensate for load losses due to the battery.

  • Width: 600 mm
  • Bay depth: 1000 mm and 1200 mm + 250mm hydro door
  • Heights: 42U and 47U
  • Color: Black RAL 9005

Air flow regulation by measuring the differential pressure between the rack and the room, and adjusting the exchanger flow rate to the actual server flow rate: no disruption to the equipment's own regulation.
- Water flow regulation by 2 or 3-way proportional valve:
- Output temperature selected by setpoint assigned via PLC or supervision.
- No jerking of water circuit pumps: constant overall flow.

  • 2 or 3-way control valve
  • Water presence detector
  • Redundant power supply
  • Flow meter
  • Airflow control by return air temperature
  • HPC computing centers
  • THD data center equipment